{"en":"NGF Series Stailess Steel Hollow Cooling Tower Fan","es":"","ru":"","zh-cn":"NGF系列不锈钢空心冷却塔风机"}

NGF Series Stailess Steel Hollow Cooling Tower Fan

NGF Series Stailess Steel Hollow Cooling Tower Fan

NGF series stainless steel hollow type cooling tower fans are designed specifically for cooling tower, offering distinct advantages over other types of fans. The fan delivers maximum air flow and pressure capability at reduced speed. Fan diameter is available from 2000 to 5000mm.



NJF series aluminum alloy hollow type cooling tower fans are designed specifically for cooling tower, offering distinct advantages over other types of fans. The blade enhanced for low sound operation, delivers maximum air flow and pressure capability at reduced speed. The skin of NJF fan is made with high quality aliminum alloy that is infused with pigment for even distribution across the laminate. Blades connects to the fan hub using a heavy-galvanized iron ring integrally molded with each fan blade. By loosening the hub attachment hardware, blades can easily be rotated to achieve desired pitch, permitting maximum utilization of fan horsepower.
 

Model Description


Features

High transmission efficiency: aluminum alloy airfoil blades with high transmission efficiency
Light weight: high-strength aluminum alloy material.
Good balance: the fan blades have high precision, and have been tested for weight matching and balance before delivering, the fan running balance has been modified.
Anti-corrosion ability: the surface oxidation treatment process used on the surface of the fan improves the corrosion resistance.
 

Technical Parameters

Fan blades connect to the hub is using a heavy-galvanized iron ring integrally molded with each fan blade. By loosening the hub attachment hardware, blades can easily be rotated to achieve desired pitch, permitting maximum utilization of fan horsepower.
 
      
Model
Motor 
Power (KW)
Rotate 
Speed
(rpm)
Blade
Angle
(A)
Static 
Pressure 
(Pa)
Air 
Volume 
 (m³/h)
Hub 
Heigh 
(H)
Hole 
Dia.
(Ød)
Key 
Width
(F)
Key 
Depth
(T)
NGF-2000-4
5.5
320
25
75
90000
108
38
8
3.3
30
77
100000
35
70
110000
NGF-2200-4
5.5
265
25
69
100000
123
50
12
3.3
30
73
105000
35
63
115000
NGF-2400-4
5.5
250
25
60
130000
123
50
12
3.3
30
61
140000
35
62
150000
NGF-3000-4
7.5
230
25
70
180000
138
50
12
3.3
11
30
68
200000
11
35
68
220000
NGF-3400-4
11
200
25
56
240000
148
60
12
3.3
11
30
58
270000
15
35
60
300000
NGF-3700-4
15
200
25
61
310000
158
75
20
4.9
15
30
65
340000
18.5
35
69
370000
NGF-4200-4
18.5
175
25
68
400000
158
75
20
4.9
22
30
65
440000
22
35
63
480000
NGF-5000-4
30
170
25
70
600000
158
75
20
4.9
37 30 76 640000
37 35 82 680000


Fan Assembly Instructions

Newin NJF series hollow type aluminum alloy fans are shipped in unassembled shape, fan blades and hub will be matched well to ensure proper re-assembly.
a. Select a wide open area to accommodate to the fan diameter.
b. Position the fan hub 1 in the center of the work area with the blade sockets.
c. Place fan blade 2 in a blade socket on the hub. On fans where the blades overlap at the hub be sure to have the leading edge under the trailing edge of the forward blade. 
d. Ensure the blade shank safety collar is inboard of the inner hub rim
 

Fan Installation Instructions

1. Be sure cooling tower motor is locked out.
2. Clean the hub bore and driving shaft extension for the full length of the key.
3. Insert the key in the keyway. The top of the key must be below the top of the shaft by not more than 3 mm . The key is a tight fit across the width and must never be altered.
4. After cleaning, apply a coat of anti-seize compound to the engage - ment portion of the shaft.
5. Raise the fan assembly above the shaft and slowly lower the hub onto the shaft with the keyways aligned. Make certain the key does not slide down during installation.
6. Install the Hub Retention Cap Screw with Lock Washer.

 

Application & Usage

Hollow type aluminum alloy fan is widely used in different types of cooling towers, 3 fan blades, 4 fan blades, 5 fan blades, 6 fan blades and 8 fan blades are available for different working condition and air volume conditions. Newin also supplies customized service for customers worldwide.


Fan Maintenance

Timely fan maintenance will prolong the useful life and assure continued trouble-free operation.
After the first week and subsequently at six month intervals:
•  Torque all hardware to check if any loose
•  Visually inspect the fan for airborne debris damage, check with fan cylinder segments, and corrosive attack. Correct any situations deter-mined detrimental to fan operation.
•  Remove any accumulated scale or dirt.
•  Clear blade drain holes at fan tip.


Filed Data for Replacing Cooling Tower Fan 

Newin supplys cooling tower replacement service for brand cooling towers. Inform us below required information so that we could offer correctly: 1. Fan Diameter,  2. Nos of Fan Blades ,  3. Blade Width ,  4. Hub diameter
To match your existing driving shaft, shaft diameter, key width and hub height are also required when placing orders.
 

Please make sure your contact information is correct. Your message will be sent directly to the recipient(s) and will not be publicly displayed. We will never distribute or sell your personal information to third parties without your express permission.

Related Parts