{"en":"CF Series Aluminum Alloy Solid Type Cooling Tower Fan","es":"","ru":"","zh-cn":"CF系列铝合金整体式冷却塔风机"}

CF Series Aluminum Alloy Solid Type Cooling Tower Fan

CF Series Aluminum Alloy Solid Type Cooling Tower Fan

CF series aluminum alloy hollow type cooling tower fans are designed specifically for cooling tower, offering distinct advantages over other types of fans. The blade enhanced for low sound operation, delivers maximum air flow and pressure capability at reduced speed. 


CF series aluminum alloy solid type cooling tower fans are designed specifically for cooling tower, offering distinct advantages over other types of fans. The blade enhanced for low sound operation, delivers maximum air flow and pressure capability at reduced speed. The skin of NJF fan is made with high quality aliminum alloy that is infused with pigment for even distribution across the laminate. Blades connects to the fan hub using a heavy-galvanized iron ring integrally molded with each fan blade. By loosening the hub attachment hardware, blades can easily be rotated to achieve desired pitch, permitting maximum utilization of fan horsepower.
 

Model Description


Features

■ High quality Aluminum material fan blades
■ Connects heavy-galvanized iron fan hub, easy installation and adjustable blade angle

■ Beautiful and concise, good corrosion resistance
■ High precision, low noise and high efficiency


Technical Parameters

Fan blades connect to the hub is using a heavy-galvanized iron ring integrally molded with each fan blade. By loosening the hub attachment hardware, blades can easily be rotated to achieve desired pitch, permitting maximum utilization of fan horsepower.
Model
Motor 
Power 
(KW)
Rotate 
speed  
  (rpm)
Blade
 angle  
 (A)
Static 
pressure 
(Pa)
Air 
volume 
 (m³/h)
Hub 
Heigh 
  (H)
Shaft 
Diameter 
 (Ød)
Key 
width 
 (F)
Key 
Depth
(T)
CF-1184-4
1.1
720
18
73
28000
63/83
28
8
3.3
1.5
21
71
32000
1.5
24
62
36000
CF-1500-4
2.2
460
18
70
45000
83
34
8
3.3
21
70
50000
24
65
55000
CF-1800-4
4
365
18
66
70000
108
38
8/10
3.3
21
69
75000
24
60
85000
CF-2000-4
5.5
320
18
75
90000
108
38
8
3.3
21
77
100000
24
70
110000
CF-2200-4
5.5
265
18
69
100000
123
50
12
3.3
21
73
105000
24
63
115000
CF-2400-4
5.5
250
18
60
130000
123
50
12
3.3
21
61
140000
24
62
150000
CF-3000-4
7.5
230
17
70
180000
138
50
12
3.3
11
20
68
200000
11
23
68
220000
CF-3400-4
11
200
17
56
240000
148
60
12
3.3
11
20
58
270000
15
23
60
300000
CF-3700-4
15
200
16
61
310000
158
75
20
4.9
15
19
65
340000
18.5
22
69
370000
CF-4200-4
18.5
175
16
68
400000
158
75
20
4.9
22
19
65
440000
22
22
63
480000
CF-5000-4
30
170
14
70
600000
158
75
20
4.9
37
17
76
640000
37
20
82
680000

    
Fan Assembly Instructions

Newin CF series solid type aluminum alloy fans are shipped in unassembled shape, fan blades and hub will be matched well to ensure proper re-assembly.
a. Select a wide open area to accommodate to the fan diameter.
b. Position the fan hub 1 in the center of the work area with the blade sockets.
c. Place fan blade 2 in a blade socket on the hub. On fans where the blades overlap at the hub be sure to have the leading edge under the trailing edge of the forward blade. 
d. Ensure the blade shank safety collar is inboard of the inner hub rim
 

Application & Usage

Solid type aluminum alloy fan is widely used in different types of cooling towers, mostly in 4 fan blades. Newin also supplies customized service for customers worldwide.


Fan Maintenance

Timely fan maintenance will prolong the useful life and assure continued trouble-free operation.
After the first week and subsequently at six month intervals:
•  Torque all hardware to check if any loose
•  Visually inspect the fan for airborne debris damage, check with fan cylinder segments, and corrosive attack. Correct any situations deter-mined detrimental to fan operation.
•  Remove any accumulated scale or dirt.
•  Clear blade drain holes at fan tip.


Filed Data for Replacing Cooling Tower Fan 

Newin supplys cooling tower replacement service for brand cooling towers. Inform us below required information so that we could offer correctly: 1. Fan Diameter,  2. Nos of Fan Blades ,  3. Blade Width ,  4. Hub diameter
To match your existing driving shaft, shaft diameter, key width and hub height are also required when placing orders.
 

Please make sure your contact information is correct. Your message will be sent directly to the recipient(s) and will not be publicly displayed. We will never distribute or sell your personal information to third parties without your express permission.

Related Parts