{"en":"NBD Series Drift Eliminator","es":"","ru":"","zh-cn":"NBD系列收水器"}

NBD Series Drift Eliminator

NBD Series Drift Eliminator

NBD series drift eliminators are designed to capture large water droplets caught in the cooling tower air stream.The eliminators prevent the water droplets and mist from escaping the cooling tower.


Newin NBD series blade type drift eliminators is applicable to large and medium natural ventilation cooling towers and mechanical ventilation cooling towers.It can remove a large number of small water droplets carried by hot and humid air from cooling towers and avoid pollution to the surrounding environment.After installation, the water mist escape rate decreases from 0.1% when the dehydrator is not installed to 0.05%, but the eliminator has no obvious influence on the cooling water temperature.A set contains eliminator sheets and spacer, PVC rods, PVC nuts.
 

Features

■ There are different types, V type, S type, M type, mutiwave type and replacement for other brand cooling towers.
■ Made of flame retardant PVC material, PP material for options if special needed.
■ Anti-aging, high water absorption, low airflow resistance, high strength, easy installation and long service life.
■ Easy installation with rods and screws.
 

Properties 

With different request in NBD drift eliminators, like length and width, materials or thickness, etc, please inform us your detailed request to get correct solution and offer. Newin could cover all customer requirements. Eliminator media in flame retardant or anti-bacterial execution are also available on request.
Module Length (Max)  mm 2000
Module Width  (Max)  mm 500 / 1000
Module Depth   mm 160 / 175 / 220
Flute Height  mm 25/45/50
Flute Corrugation Angle  degrees
Sheet Thickness - Before Forming  mm 0.8
Sheet Thickness - After  Forming  mm 0.6
Max. application temp. (short time) - PVC  °C 60
Max.operating temp. (short time) - PP.  °C 95
Customized size and thickness available for special request. Contact Newin for details.
 

Structure & Installation Drawing

Newin supply structure & installtion drawing advice with jobsite storage advice and quality control report along with shipment to make attention to customers when they receive the materals. OEM or special mold design also available on request.



Application & Usage

Newin NBD blade drift eliminator is applicable counter flow cooling tower with SGS test in ASTM Standards to keep high quality drift eliminator to get the high efficiency of the cooling tower. Inform us the tower model or size, we will estimate the Nos of sheets needed for your cooling tower replacing.


Applicable Commercial Standards

Sheets material is strictly followed below SGS test with ASTM standards. Each property or all properties as below tested by your products are also vailable on request.
Property Test Method Values
Specific Gravity ASTM D792-13
Method B
1.426g/cm3
Oxygen Index ASTM D2863-13 34.50%
Tear Strength ASTM D1004-13 X direction 111 N
Y direction 121 N
Tensible Test ASTM D 882-12 Tensile Strength X direction 51.1 MPa
Y direction 45.3 Mpa
Elongation at
Break
X direction 87%
Y direction 56%
Values shown above based on SGS Test No.: GZIN1708039662PS by Newin
Statements and methods presented are based upon the best available information and practices 
known to Newin. Conditions of use may vary and are beyond control, the user should undertake 