{"en":"BAD Celluar Drift Eliminator","es":"","ru":"","zh-cn":"BAD系列收水器"}

BAD Celluar Drift Eliminator

BAD Celluar Drift Eliminator

BAD celluar drift eliminator removes small droplets of water that are entrained in the exhaust air to minimize the nuisance and health issues that they create if allowed to escape through the top of the tower along with the heated air. 


Newin BAD celluar drift eliminator removes small droplets of water that are entrained in the exhaust air to minimize the nuisance and health issues that they create if allowed to escape through the top of the tower along with the heated air. BAD series drift eliminators are designed to create a tortuous path for the air stream. When the water droplets move through them, they are forced to change direction and impact the drift eliminator side walls, coalescing and draining back into the wet section of the cooling tower.
 

Features

■ Anti-aging, high water absorption.
 low airflow resistance, high strength.
 easy installation and long service life.
 can be the replacement of air inlet louver.
 

Properties 

With different request in BAD drift eliminators, like length and width, materials or thickness, etc, please inform us your detailed request to get correct solution and offer. Newin could cover all customer requirements. Fill media in flame retardant or anti-bacterial execution are also available on request.
Module Length (Max)  mm 2440
Module Width  (Max)  mm 500
Module Height  mm 140
Flute Height  mm 25
Sheet Thickness - Before Forming  mm 0.45
Sheet Thickness - After  Forming  mm 0.38
Max. application temp. (short time) - PVC  °C 60
Customized size and thickness available for special request. Contact Newin for details.
 

Structure & Installation Drawing

Newin supply structure & installtion drawing advice with jobsite storage advice and quality control report along with shipment to make attention to customers when they receive the materals. OEM or special mold design also available on request.


Application & Usage

Newin BAD celluar drift  eliminator is applicable for replacing counter flow cooling towers and cross flow cooling towers, with SGS test in ASTM Standards to keep high quality infill to get the high efficiency of the cooling tower. Inform us the tower model or size, we will estimate the Nos of sheets needed for your cooling tower replacing.


Applicable Commercial Standards

Sheets material is strictly followed below SGS test with ASTM standards. Each property or all properties as below tested by your products are also vailable on request.
Property Test Method Values
Specific Gravity ASTM D792-13
Method B
1.426g/cm3
Oxygen Index ASTM D2863-13 34.50%
Tear Strength ASTM D1004-13 X direction 111 N
Y direction 121 N
Tensible Test ASTM D 882-12 Tensile Strength X direction 51.1 MPa
Y direction 45.3 Mpa
Elongation at
Break
X direction 87%
Y direction 56%
Values shown above based on SGS Test No.: GZIN1708039662PS by Newin
Statements and methods presented are based upon the best available information and practices 
known to Newin. Conditions of use may vary and are beyond control, the user should undertake 
sufficient tests to determine the suitability for any intended use of the material.
  